Palm329 va ditto hj panel breakers are sized for the wire.
Breaker and wire size for 4500 watt water heater.
This means that 10 copper wire will also be used.
4500 watt vs 5500 watt.
A standard 3000 watt heater will use a two pole 20 amp breaker connected to.
The higher the wattage the larger the wire size.
80 of breaker max single phase breaker size wire size based on copper thhn wire increase one size when using aluminum conductors at 115 volts at 230 volts 15 amp 14 1 380 2 760 20 amp 12 1 840 3 680.
You have stated that the calculated amperage load for 4500watt at 240volts is 18 75amps however nec article 422 13 states that the minimum circuit rating for a water heater must be 125 of the rated load so this 4500watt load requires a minimum circuit of 23 44 amps at 240volts.
The wire size is dependent upon the wattage size of your water heater.
Multiply the value for current by 125 percent to determine the size of the breaker you need for the heater.
4500 watt vs 5500 watt.
In a us household the current draw for a 1500 watt water heater is 12 5 amps.
Multiply the current rating of the water heater with 125.
Now lets consider this water heater circuit installation.
Now in order to choose an electric breaker multiply the current draw of the water heater with 125 per cent in order to determine the size of the breaker you will need.
A 1500 watt heater on a 120 volt circuit thus needs a breaker of 15 6 amps.
If it s 4500 then the 20 amp will work but it won t be code compliant.
4500 240 18 75 amps will work on a 20 amp ocpd but.
60 amp is correct for such use.
Now a 3800 watt heater will draw around 15 8 amps.